Question

Match the workability tests with their measurements for fresh concrete. Workability test Measurement (A) Slump test (1) 300 mm to 500 mm (B) Compacting factor (2) 75 mm to 125 mm (C) Vee Bee test (3) 0 .80 to 0.98 (D) Flow test (4) Zero to 10 s

A

A - 4, B - 3, C - 2, D - 1

B

A - 2, B - 4, C - 3, D - 1

C

A - 2, B - 1, C - 4, D - 3

D

A - 2, B - 3, C - 4, D - 1

Text Solution
Verified by Experts

Concept:

Measurement of workability of concrete:

Slump test:

  • This method of test specifies the procedure to be adopted, either in the laboratory or during the progress of work in the field, for determining the consistency of concrete where the nominal maximum size of the aggregate does not exceed 38 mm.
  • The internal dimensions of the mould are bottom diameter = 200 mm, top diameter = 100 mm, and height = 300 mm.
  • The mould is filled in with fresh concrete in four layers, each approximately one-quarter of the height, and tamped with twenty-five strokes of the rounded end of the tamping rod.
  • Generally, we measure the workability of concrete varies from 25 mm to 150 mm.
SI No. Degree of workability Slump value
1. Very low < 25 mm
2. Low 25 mm - 75 mm
3. Medium 75 mm - 100 mm
4. High 100 mm - 150 mm
5. Very high > 150 mm

Compaction Factor Test:

  • In the compaction factor test the degree of workability of concrete is measured in terms of internal energy required to compact the concrete thoroughly.
  • A compaction factor of 0.95 represents flowing concrete having high workability, a compaction factor of 0.92 plastic concrete having medium workability, a compaction factor of 0.85 stiff plastic concrete having low workability, and a compaction factor of 0.75 represents stiff concrete having very low workability.
  • The compacting factor test is designed primarily for use in the laboratory but it can also be used in the field.
  • The degree of compaction called the compacting factor is measured by the density ratio i.e., the ratio of the density actually achieved in the test to the density of the same concrete fully compacted.

Vee-Bee Test:

  • This is carried out in such a manner that the specimen concrete in the test receives more or less same treatment in respect of the method of placing as it would in the actual execution of the work. 
  • This test is preferred for finding the workability of stiff concrete mix having very low workability. 
  • In this test, a Vee-Bee time of 3 to 0 seconds represents very high workability, a Vee-Bee time of 5 to 3 seconds represents stiff plastic concrete having medium workability, 10 to 15 seconds represents stiff concrete of low workability, and a Vee-Bee time of 18 to 10 seconds represents very stiff concrete having very low workability.

Flow Table Test:

  • This is a laboratory test that gives an indication of the quality of concrete with respect to consistency cohesiveness and proneness to segregation.
  • This test is done for concrete having very high workability (up to 500 mm slump value).
  • Consists of a circular table and mould in the form of frustum (top diameter is 17 cm, bottom diameter is 25 cm, and height is 12 cm).
  • The spread or the flow of the concrete is measured and this flow is related to workability.

F l o w % = S p r e a d o f c o n c r e t e i n c m 25 25 × 100

  • The value could range anything from 0 to 150%.

Thus the correct match is A → 2, B → 3, C → 4, and D → 1. Hence option (4) is correct.