Question

Cleaning of transformer and oil leakage at joints is done on a ______ basis.

A

quarterly

B

yearly

C

daily

D

weekly

Text Solution
Verified by Experts

The correct answer is (option 2) i.e. yearly.

Explanation:

  • The transformer undergoes regular maintenance in yearly basis to check the Transformer insulation i.e. oil leakage, dielectric strength, etc.

Daily Basis Maintenance and Checking:

  • There are three main things which to be checked on a power transformer on a daily basis are
  1. Reading of MOG (Magnetic Oil Gauge) of main tank and conservator tank.
  2. Color of silica gel in breather.
  3. Leakage of oil from any point of a transformer.

 

  • In case of an unsatisfactory oil level in the MOG, oil to be filled in transformer and also the transformer tank to be checked for oil leakage. If oil leakage is found take the required action to plug the leakage. If silica gel becomes pinkish, it should be replaced.


Monthly Basis Maintenance of Transformer:

  1. The oil level in the oil cap under the silica gel breather must be checked in a one-month interval. If it is found the transformer oil inside the cup comes below the specified level, oil to be top-up as per the specified level.
  2. Breathing holes in silica gel breather should also be checked monthly and properly cleaned if required, for proper breathing action.
  3. If the transformer has oil-filled bushing the oil level of transformer oil inside the bushing must be checked in the oil gage attached to those bushing.

 

  • If it is required, the oil to be filled in the bushing up-to-the correct level. Oil filling to be done under the shutdown condition.

Maintenance of Transformer on Half Yearly Basis:

  • The transformer oil must be checked half-yearly basis that means once in 6 months, for dielectric strength, water content, acidity, sludge content, flash point, DDA, IFT, resistivity for transformer oil.
  • In the case of a distribution transformer, as they are operating light load conditions all the time of day remaining peak hours, so there is no maintenance required.


Yearly Basis Transformer Maintenance Schedule:

  • The auto, remote, manual function of the cooling system that means, oil pumps, air fans, and other items engaged in the cooling system of the transformer, along with their control circuit to be checked in the interval of one year. In the case of trouble, investigate the control circuit and physical condition of pumps and fans.
  • All the bushings of the transformer to be cleaned by soft cotton cloths yearly. During cleaning the bushing should be checked for cracking.
  • Oil condition of OLTC to be examined every year.
  • Mechanical inspection of Buchholz relays to be carried out yearly.
  • The pockets for OTI, WTI (Oil Temperature Indicator & Winding Temperature Indicator) on the transformer top cover to be checked and if required oil to be replenished.
  • The proper function of the Pressure Release Device and Buchholz relay must be checked annually.
  • Insulation resistance and polarization index of the transformer must be checked with battery-operated megger of 5 kV range.
  • Resistive value of earth connection and rizer must be measured annually with a clamp-on earth resistance meter.
  • DGA or Dissolve Gas Analysis of transformer Oil should be performed, annually for 132 kV transformer, once in 2 years for the transformer below 132 kV transformer and in 2 years interval for the transformer above 132 kV transformer.

Updated on:21/07/2023